SGRL, SGWL, SCRL, SCWL, SCWL-CLR-ALERT, SRL, SRL-P, SRL-SP, SWL, SWL-ALERT, SWL-CLR-ALERT, SWL-P
หมวดหมู่ : FIRE ALARM ,  NOTIFIER , 
แบรนด์ : NOTIFIER
Share
Strobes are available in ceiling-mount or wall-mount varieties to meet a wide variety of applications. They are ideal for warning hearing-impaired individuals during an emergency event. To expand the versatility of stobes, colored lenses are sold separately as accessories.
Features & Benefits
-Plug-in design and protective cover reduce ground faults
-Universal mounting plate with an onboard shorting spring tests wiring continuity before installation
-Automatic selection of 12- or 24-volt operation at 15 and 30 candela
Specifications
-Standard Operating Temperature 32°F to 120°F (0°C to 49°C)
-Humidity Range 10 to 93% non-condensing
-Strobe Flash Rate 1 flash per second
-Nominal Voltage Regulated 12VDC or regulated 24DC/FWR1
-Operating Voltage Range 8 to 17.5V (12V nominal) or 16 to 33V (24V nominal)
-Electrically compatible with System Sensor Sync Circuit listed to UL 464
-Compatible with previous designs dating back to 1997
-Input terminal wire gauge 12 to 18 AWG
Listings:
-UL 1791
-FM
-CSFM