RP-2001 is a UL listed six-zone fire alarm control panel for single and dual hazard deluge and preaction applications, providing fire detection, signaling and protection for commercial, industrial and institutional buildings requiring water-based releasing.
Features & Benefits:
Designed for sprinkler standards NFPA 13, 15 and 16.
Dual hazard operation.
Cross-zone (double-interlock) capability.
Six programmable Style B (Class B) IDCs (Initiating Device Circuit).
Optional Digital Alarm Communicators
Specifications
-Initiating Device Circuits: 6 Class B
-Output Circuits: 4 Class B; rated at 3 amp
-Discharge Timer: Yes, programmable
-Soak Timer: Yes
-Cross Zone/Interlock: Yes
-Relays: 3 Form-C; programmable
-Annunciators: Yes; up to 8 LCD Display: 80 character LCD
-Power: 7.0 amps total system power
Listings:
-UL: S635
-FM approved
-CSFM: 7165-0028:0245
-MEA: 333-07-E